Units, signs and data updates

How to read the numbers the API returns, how fresh they are and how often it makes sense to ask for them.

Units

Quantity Unit Type
Power W integer
Energy Wh integer, always ≥ 0
State of charge % number, 0–100

Signs

Grid and battery power carry a sign:

Field Positive Negative
grid_power_w import from the grid export to the grid
battery_power_w battery charging battery discharging

Energy values, instead, are never negative: the direction is in the field name (imported / exported, charged / discharged).

Timestamps

  • Telemetry, connectivity and alarm timestamps are ISO 8601 in UTC (2026-10-13T12:21:00Z).
  • Energy windows (period_start, period_end, timestamp_start, timestamp_end) are ISO 8601 in the plant's time zone, with its offset (2026-10-13T00:00:00+02:00).
  • State of charge is per gateway, never a plant average.

How often data is updated

Data How it is produced Practical consequence
Power one sample per gateway every 60 s polling more often returns the same sample
Online status data received in the last 5 minutes a plant goes offline 5 minutes after its last sample
Energy 15-minute counters today's totals trail real time by about 15 minutes

The null rule on telemetry/latest

telemetry/latest returns samples of the last 5 minutes only. When the plant sent no data in that time, the response is still 200, with "timestamp": null and "measurements": null: an old value is never returned. A null therefore means "no recent data", not "zero"; to see since when the plant has been silent, check last_seen_at in the connectivity.

Inside measurements, pv_power_w and load_power_w read 0 on plants that do not measure them; they are null only in telemetry/series samples. Always handle null as a possible value for power, state of charge and energy.

Pattern for a fleet of up to 100 plants, that is one bulk page:

Call Interval Requests per day
GET /v1/telemetry/latest 60 s 1 440
GET /v1/connectivity 5 min 288
GET /v1/energy/totals?period=day 15 min 96
Total ≈ 1 800
  • Shorter intervals do not give fresher data: they return the same samples.
  • Read power series, energy series and alarms per plant only when you need them.
  • Each extra bulk page multiplies the requests: beyond 100 plants this pattern exceeds the daily limit (see "Limits, errors and support"), so lengthen the intervals or ask for a dedicated agreement.